Description
Compact stand-alone data logger from Delphin Technology.
The Loggito Logger is an autonomous data logger with internal measurement data storage capabilities. Integrated software channels enable easy configuration of monitoring and calculation procedures. The device has an extended range of possible applications, including monitoring and alerting.
Loggito Gate version is the ideal solution for logging and recording machine data in measurement networks, as well as for control. With the integrated Ethernet connection and the available OPC UA (server/client) and Modbus TCP standards, it can be used multifunctionally. From a pure Modbus or OPC logger to a transmission solution in a DAQ software, many applications are possible.
The Loggito USB is an entry-level version in Delphin’s measurement technology. Loggito USB can be used either for PC-based measurement or as an extension to the Loggito Logger.
Product Features
- Up to 8 universal analogue inputs
- Digital inputs or switching outputs
- Very compact design
- Flexible sampling rate for a wide range of applications
- Simple configuration
- Detachable spring-clamp terminals for easy connection
- Reliable monitoring and alerting
Sensor Connection
- Universal analogue inputs (mV, mA, thermocouples, optional RTD)
- Digital inputs can also be used as frequency and pulse counters
- Pluggable spring-clamp terminals
- Clear connection diagram for simple wiring

Interfaces
- LAN interface (only with Loggito Logger)
- USB interface
- Modbus TCP (optional and only with Loggito Logger)
- OPC UA (optional and only with Loggito Logger)
- WLAN (optional and only with Loggito Logger)
Data Storage (Loggito Logger only)
- 16 GB internal storage
- External storage media (USB, NFS, CIFS, (S)FTP)
- Event-triggered recording with pre and post histories
- Push function
Applications
- Automated trials, testing and inspection
- Building monitoring
- Facility monitoring
- Cold store monitoring
- Mobile data acquisition
- Low-power applications, e.g. in environmental measurement technology
- Test stands
- School and university experimental areas
- Laboratory data acquisition
- Decentralised data acquisition
- Temperature acquisition
- Servicing and start-up
- Monitoring and alerting
- Mobile measuring
Channel Type |
8 AI-RTD
|
8 AI
|
4 AI-RTD
|
4 AI
|
Analogue Inputs |
8 |
8 |
4 |
4 |
Appropriate for RTD's |
4 |
0 |
2 |
0 |
Sensors |
mV, mA, thermocouples, RTD's (no RTD's with channel types 8 AI and 4 AI) |
Total Sampling Rate |
0.1 Hz to 500 Hz |
Voltage Measurement Range |
±78 mV to ±10 V |
Current Measurement Range |
0 to 20 mA / 4 to 20 mA / ±20 mA / any (with freely selectable external shunts) |
Resistance Measurement Range |
0 to 49 kΩ |
Resolution / Type ADC |
24 bit Sigma-Delta |
Input Impedance |
> 5GΩ |
Isolation |
±24 VDC |
Max. Differential Voltage Channel to Channel |
±24 VDC |
Galvanic Isolation Against FE |
±400 VDC |
Measuring Accuracy Voltage, Current |
0.01% from upper range value |
Measuring Accuracy Resistance Measurement |
0.01% of the measuring range end value (4-wire connection)
0.1% of the measuring range end value (3-wire connection after additional offset determination) |
Measuring Accuracy Thermocouples* |
0.1 % from measuring range after sensor compensation |
Measuring Accuracy Pt 100 (4-wire connection) |
Measuring range -260 °C to 147 °C: 0.10 °C
Measuring range -260 °C to 596 °C: 0.10 °C
Measuring range -260 °C to 849 °C: 0.22 °C |
Measuring Accuracy Pt 1000 (4-wire connection)
|
Measuring range -260 °C to 64 °C: 0.10 °C
Measuring range -260 °C to 408 °C: 0.10 °C
Measuring range -260 °C to 849 °C: 0.18 °C |
* These measuring accuracies apply to positive measuring temperatures (> 0°C). For measurements in the negative temperature range, we recommend calibration at the respective operating point.
Channel Type
|
8 AI-RTD
|
8 AI
|
4 AI-RTD
|
4 AI
|
Digital / Frequency Inputs or rather
Digital / PWM Outputs (switchable) |
2 |
2 |
2 |
2 |
Input Signal |
low: 0 to 1 V / high: 3.6 to 100 VDC@3.5 mA |
Frequency Input Measuring Range |
0.2 Hz to 500 Hz |
Counter Width |
64 bit |
Max. Switching Voltage / Current |
50 V / 2.5 A for 2 seconds, 250 mA continuous current |
PWM Basic Frequency / Duty Cycle |
100 Hz / 1:20 |
Galvanic Isolation |
± 400 VDC against FE / other channel groups |
Module type
|
Loggito Logger / Gate
|
Loggito USB
|
Interfaces
|
LAN |
10BASE-T/100-BASE-TX |
- |
WLAN |
802.11b/g/n, max. 72 MBit/s (optional) |
- |
USB device – mini socket |
2.0 low/full/high speed |
2.0 low/full speed |
USB host – type A socket |
2.0 low/full/high speed |
- |
Protocols
|
TCP/IP |
Modbus TCP Client (optional)
Modbus TCP Server
OPC UA Client (optional)
OPC UA Server
OPC UA HA Server (optional)
NTP, SMTP, PTP |
- |
Data storage
|
Internal |
16 GB (approx. 30 million measured values per GB) |
|
External |
USB, NFS, CIFS, (S)FTP |
- |
General technical information
|
Dimensions |
approx. L 95 mm x W 67 mm x H 65 mm |
Weight |
approx. 220g |
Fixing |
mounting rail DIN EN 60715 or screw mounting horizontally / vertically or upwards |
Connecting terminals |
plug-in spring terminals, max. 24 terminals in 2 rows,
conductor cross-section (rigid / flexible) 0.2 to 2.5 mm², ferrule 0.25 to 1.5 mm² |
Temperature range |
-20 to 60° C |
Humidity |
max. 90 % relative humidity, non-condensing |
Supply voltage |
12 to 24 VDC / ±10 % |
5 VDC
(via mini USB connector) |
Power input |
max. 7.5 watts |
max. 2.5 watt |