UK Supplier of Data Acquisition & Thermal Imaging systems, software and services

Search

Loggito Series

Loggito is a compact measuring system that doesn’t compromise on quality. You can use Loggito as a low-channel data logger or as part of a complex measuring network with distributed measuring points, fully tailored to your needs. It requires minimum space so is quick and easy to retrofit into your existing systems.

Manufacturer:

Call for price

Description

Compact stand-alone data logger from Delphin Technology.

The Loggito Logger is an autonomous data logger with internal measurement data storage capabilities. Integrated software channels enable easy configuration of monitoring and calculation procedures. The device has an extended range of possible applications, including monitoring and alerting.

Loggito Gate version is the ideal solution for logging and recording machine data in measurement networks, as well as for control. With the integrated Ethernet connection and the available OPC UA (server/client) and Modbus TCP standards, it can be used multifunctionally. From a pure Modbus or OPC logger to a transmission solution in a DAQ software, many applications are possible.

The Loggito USB is an entry-level version in Delphin’s measurement technology. Loggito USB can be used either for PC-based measurement or as an extension to the Loggito Logger.

Product Features

  • Up to 8 universal analogue inputs
  • Digital inputs or switching outputs
  • Very compact design
  • Flexible sampling rate for a wide range of applications
  • Simple configuration
  • Detachable spring-clamp terminals for easy connection
  • Reliable monitoring and alerting

Sensor Connection

  • Universal analogue inputs (mV, mA, thermocouples, optional RTD)
  • Digital inputs can also be used as frequency and pulse counters
  • Pluggable spring-clamp terminals
  • Clear connection diagram for simple wiring

Loggito Channel Summary

Interfaces

  • LAN interface (only with Loggito Logger)
  • USB interface
  • Modbus TCP (optional and only with Loggito Logger)
  • OPC UA (optional and only with Loggito Logger)
  • WLAN (optional and only with Loggito Logger)

Data Storage (Loggito Logger only)

  • 4 or 8 GB internal storage
  • External storage media (USB, NAS)
  • Event-triggered recording with pre and post histories
  • Push function

Applications

  • Automated trials, testing and inspection
  • Building monitoring
  • Facility monitoring
  • Cold store monitoring
  • Mobile data acquisition
  • Low-power applications, e.g. in environmental measurement technology
  • Test stands
  • School and university experimental areas
  • Laboratory data acquisition
  • Decentralised data acquisition
  • Temperature acquisition
  • Servicing and start-up
  • Monitoring and alerting
  • Mobile measuring
Module Type
Loggito Series
Analogue inputs
Sensors mV, mA, thermocouples, RTDs (no RTDs with channel types 8 AI and 4 AI)
Total sampling rate 0.1 Hz to 500 Hz
Voltage measurement range ±78 mV to ±10 V
Current measuring range 0 to 20 mA / 4 to 20 mA / ±20 mA / any (with freely selectable external shunts)
Resistance measurement range 0 to 49 kΩ
Resolution/Type ADC 24 bit Sigma-Delta
Input impedance > 5GΩ
Dielectric withstand voltage
(tolerable overvoltage)
±24 VDC
Max. differential voltage channel to channel ±24 VDC
Galvanic isolation against FE ±400 VDC
Precision of current and voltage measurement 0.01% from upper range value
Precision resistance measurement 0.01% from upper range value (4-wire connection),
0.1% from upper range value (3-wire connection after additional offset determination)
Measuring accuracy thermocouples*
0.1 % from measuring range after sensor compensation
Measuring accuracy Pt 100 (4-wire connection) Measuring range -260 °C to 147 °C: 0.10 °C
Measuring range -260 °C to 596 °C: 0.10 °C
Measuring range -260 °C to 849 °C: 0.22 °C
Measuring accuracy Pt 1000 (4-wire connection) Measuring range -260 °C to 64 °C: 0.10 °C
Measuring range -260 °C to 408 °C: 0.10 °C
Measuring range -260 °C to 849 °C: 0.18 °C
Digital / frequency inputs
Input signal low: 0 to 1 V / high: 3.6 to 100 VDC@3.5 mA
Frequency input measuring range 0.2 Hz to 500 Hz
Counter width 64 bit
Galvanic isolation ±400 VDC against FE / other channel groups
Digital / PWM outputs
Max. switching voltage / current 50 V / 2.5 A for 2 seconds, 250 mA continuous current
PWM basic frequency / duty cycle 100 Hz / 1:20
Galvanic isolation ±400 VDC against FE / channels of other groups

* These measuring accuracies apply to positive measuring temperatures (> 0°C). For measurements in the negative temperature range, we recommend calibration at the respective operating point.

Module type
Loggito Logger / Gate
Loggito USB
Interfaces
LAN 100 Base-Tx -
WLAN 802.11b/g/n, max. 72 MBit/s (optional) -
USB device – mini socket 2.0 low/full/high speed 2.0 low/full speed
USB host – type A socket 2.0 low/full/high speed -
Protocols
RS 232/485 (via USB extension) Modbus RTU Master, Modbus RTU slave, SCPI, ASCII -
TCP/IP Modbus TCP Client (optional)
Modbus TCP Server
OPC UA Client (optional)
OPC UA Server
OPC UA HA Server (optional)
NTP, SMTP, PTP
-
Data storage
Internal 4 / 8 GB / approx. 30 million measurement values per GB -
External USB, NFS, CIFS, (S)FTP -
General technical information
Dimensions approx. L 95 mm x W 67 mm x H 65 mm
Weight approx. 220g
Fixing mounting rail DIN EN 60715 or screw mounting horizontally / vertically or upwards
Connecting terminals plug-in spring terminals, max. 24 terminals in 2 rows,
conductor cross-section (rigid / flexible) 0.2 to 2.5 mm², ferrule 0.25 to 1.5 mm²
Temperature range -20 to 60° C
Humidity max. 90 % relative humidity, non-condensing
Supply voltage 12 to 24 VDC / ±10 % 5 VDC
(via mini USB connector)
Power input max. 7.5 watts max. 2.5 watt
Delphin Product Catalogue 2022 Delphin Product Catalogue 2022