UK Supplier of Data Acquisition & Thermal Imaging systems, software and services

Search

SS3016 – 4ch mV – Tc Modbus RS-485 IO Module

The SS3016 IO Module is able to acquire up to 4 analogue input signals, data values are transmitted with MODBUS RTU/ASCII protocol on the RS-485 network (RS232 interface is available.)

SKU SS3016 Category
Manufacturer:

Call for price

Description

4ch mV – Tc Modbus RS-485 IO Module from Sielco Sistemi.

Connect Thermocouples or up to +/- 1V voltage signals. The Cold Junction compensation for thermocouples is performed internally. By means of a 16 bit converter, the device guarantees high accuracy and stable measurements versus time and temperature. Additionally, to ensure safety, two Watch-Dog timer alarms are provided.

The 2000 Vac isolation between input, power supply and serial line removes eventual ground-loop effects. This allows you to use this device in heavy environmental conditions.
The SS3016 is in compliance with the 89/336/EEC directive on the electromagnetic compatibility. The device is housed in a rough self-extinguishing plastic container. Furthermore, thanks to its thin profile of only 17.5mm, you can mount the SS3016 on a high density EN-50022 standard DIN rail.

The SS3016 is designed to work with the MODBUS RTU/ASCII protocol: standard protocol in field-bus. This allows you to directly interface the SS3000 series devices to most PLCs and SCADA applications available on the market.

Product Features

  • Field-Bus remote data acquisition
  • RS-485 Master/Slave communication type
  • MODBUS RTU/ASCII
  • 4 channel input
  • Up to +/- 1V and Tc configurable input
  • Watch-Dog Alarm
  • Remotely Configurable
  • 2000 Vac 3-way Galvanic Isolation
  • High Accuracy
  • EMC compliance – CE mark
  • DIN rail suitable mounting – EN-50022 compliance

For more information and protocol instructions, please see the specifications sheet and user manual.

Typical @ 25°C and in the nominal conditions

Voltage Input 25mV: -25 to +25 mV
100mV: -100 to + 100 mV
250mV: -250 to +250 mV
1000mV: -1000 to +1000 mV
Thermocouple J: -210 to +1200 °C
K: -210 to +1372 °C
R: -50 to +1767 °C
S: -50 to +1767°C
B: +400 to +1825 °C
E: -210 to +1000 °C
T: -210 to +400 °C
N: -210 to +1300 °C
Input Calibration ±0.05 % or 5µV f.s.
Pot.: ±0.05 % f.s.
Linearity mV ±0.1 %
Tc ±0.2 %
Cold Junction Compensation ±0.5 °C
Input Impedance mV,Tc >1MΩ (10MΩ pull-up resistor)
Thermal Drift ±0.005 % / °C f.s.
CJC Thermal Drift ±0.02 °C/ °C f.s.
Lead wire resistance influence mv,Tc <0.8µV/Ω f.s.
Rise Time 0.5 to 2 sec
Data Transmission Baud Rate: 38.4 Kbps
Max Distance: 1.2 Km
Warm-up Time 3 min.
Power Supply Voltage 10 to 30 Vdc
Power Supply Current Consumption 30 mA @ 24 Vdc
Power Supply Polarity Inversion Protection 60 Vdc max
Isolation Input - RS485: 2000 Vac 50 Hz, 1 Min.
Supply - Input: 2000 Vac 50 Hz, 1 Min.
Supply - RS485: 2000 Vac 50 Hz, 1 Min.
Operating Temperature -10 to +60 °C
Storage Temperature -40 to +85 °C
Humidity (non condensing) 0 to 90 %
Housing Material Self-extinguishing plastic
Mounting EN-50022 DIN rail
Weight ∼ 150 g
EMC EN 61000-6-2
EN 61000-6-4
IOlog SS3016 Specifications IOlog SS3016 Specifications

IOlog SS3016 User Guide IOlog SS3016 User Guide

Request further information on this product below