Currents AC TRMS
|
| Bandwidth |
50Hz to 400Hz |
| Range |
100A, 600A |
| Resolution |
0.01A |
| Accuracy |
±(1.5% + 5dgt) |
Current DC
|
| Range |
100A, 600A |
| Resolution |
0.01A |
| Accuracy |
±(1.5% + 0.2A or 5dgt) |
Currents AC + DC (TRMS AC+DC)
|
| Accuracy |
Accuracy DC + Accuracy AC |
Voltages AC TRMS and TRMS AC+DC
|
| Bandwidth |
50Hz to 500Hz |
| Range |
100V and 1000V |
| Resolution |
10mV to 100mV |
| Accuracy TRMS AC |
±(1% + 5dgt) |
| Accuracy TRMS AC + DC |
±(1.7% + 7dgt) |
| Impedance |
3.5MΩ / 100pF |
Voltages DC
|
| Range |
100V and 1000V |
| Resolution |
10mV to 100mV |
| Accuracy |
±(0.7% + 2dgt) |
| Impedance |
3.5MΩ / 100pF |
Resistance
|
| Range |
1000Ω, 10kΩ, 100kΩ |
| Resolution |
0.1Ω to 10Ω |
| Accuracy |
±(1% + 5dgt) |
| Continuity |
with buzzer for R<30Ω
and response time of 100ms |
| Diode Test |
Yes |
Capacitance
|
| Range |
4µF to 4000µF |
| Resolution |
1nF to 1µF |
| Accuracy |
±(1.9% + 8dgt) |
Peak-Hold (current and voltage)
|
| Accuracy |
±(5dgt) |
Motor start current (Inrush)
|
| Range |
100A, 600A |
| Precision |
±(2.5% + 0.2A or 5dgt) |
Active Power
|
| Range |
10kW, 100kW and 600kW |
| Resolution |
1W to 100W |
| Accuracy |
current accuracy + voltage accuracy |
Power Factor (PF)
|
| Range |
-1.00 to 1.00 |
| Resolution |
0.01 |
| Accuracy |
±3°+1dgt |
Total harmonic distortion (THD) and distortion per harmonic
|
| Range |
0.1% to 100% |
| Resolution |
0.10% |
| Accuracy THD |
±(3% + 10dgt) |
| Accuracy per harmonics |
±(5% + 10dgt) from H01 to H12
±(10% + 10dgt) from H13 to H25 |
Frequencies
|
| Range |
20Hz to 10kHz |
| Resolution |
0.01Hz |
| Accuracy |
±(0.5% + 3dgt) |
| Sensitivity |
10% to 100% of current and voltage scales |
| Functions |
Hold, MIN / MAX / AVG Peak-Hold, automatic power-off voltage detector without contact, Low pass filter (HFR) |
| Datalogger |
9999 measurements |
| Memory |
1000 data |
General
|
| Digital Display |
Large backlight LCD screen |
| Display |
10000 dots or 4000 dots |
| Jaws Opening |
45mm |
| Max. Diameter of conductor |
37mm |
| Measurement Rate |
3 measurement/s |
| Automatic Power Off |
After 15 minutes |
| Temperature |
0°C to 50°C |
| Storage Temperature |
-20°C to 60°C |
| Protection |
Electronic on all scales |
| Safety |
600V - CAT IV and 1000V - CAT III |
| Power Supply |
1 battery 9V - 6F22 |
| Autonomy |
50h typical (battery without backlight) |
| Dimensions |
88 x 242 x 51mm |
| Weight |
435g |
| Warranty |
1 year |
Supplied with:
bag, test leads touch points, user guide, batteries |
| Optional Accessories |
flex SP295 (3000A AC, Diameter 10cm)
flex SP296 (3000A AC, diameter 18cm) |